A capacitor gives the compressor and fan motor the kick they need to start; a contactor is the switch that turns the outdoor unit on. Between them they cause many summer no-start calls, and both are tested quickly.

Answering 24/7 from our Monticello Ave office in New Orleans

  • Answering 24/7
  • Humming and no-start units
  • Tested with a meter

Updated October 2026

Short answer

When an outdoor AC unit hums but will not start, or the fan stays still while the compressor tries, a failed run capacitor is the most common cause. A contactor with pitted or burnt points makes the unit chatter, stay off, or stay on when it should stop. A technician measures the capacitor against its rated microfarads and inspects the contactor, then replaces the failed part to the unit's specification.

Signs of a failing capacitor or contactor

Humming without startingThe unit hums but the fan and compressor do not run.
Clicking or chatteringRepeated clicks from the outdoor unit.
Slow fan startThe fan starts late or needs a nudge.
Bulged capacitorThe top of the capacitor is domed or leaking.
Unit will not stopThe outdoor unit runs with the thermostat off.

What these small parts do

Technician testing an AC capacitor with a multimeter

The run capacitor stores and releases energy to start the compressor and outdoor fan and keep them running efficiently. Heat is hard on capacitors, and a unit baking in a side yard all summer wears through them. As one weakens, motors start slowly, run hot and finally will not start.

The contactor is a relay the thermostat closes to power the outdoor unit. Every start draws an arc across its points, and over the years they pit and burn. Ants are drawn to contactors as well, and a nest between the points can stop a unit cold.

Outdoor unit humming but not starting

A steady hum from the outdoor unit with the fan still and no cooling usually means a motor is getting power without enough starting torque. The usual cause is a dual run capacitor that has lost capacity or bulged at the top. Leaving the unit humming risks overheating the compressor windings, so switch it off at the thermostat. We discharge and test the capacitor with a meter, replace it with one matching the rated microfarads and voltage, and check the compressor's amp draw on restart.

Fan not spinning when the unit starts

If the compressor starts but the outdoor fan sits still, or starts only after a nudge, the fan side of the capacitor is often the weak half. A slow fan lets pressures climb and the compressor overheat. We test both sides of the dual capacitor, replace it if either side is out of range, and check the fan motor's bearings. On older units we also look at the wiring at the capacitor terminals for heat damage. If the motor itself is failing, see condenser fan motor replacement.

Pitted, burnt or stuck contactors

Worn AC contactor next to a new replacement contactor

Contactor points pit and burn a little with each start. Worn points cause chattering, a unit that will not start when the thermostat calls, or the opposite: a unit that keeps running after the thermostat is satisfied, which can freeze the coil. Ants and other insects also nest between the points. We inspect the points and coil, clear any debris, and replace a worn contactor with one rated for the unit's voltage and amps. Where repeated failures point to a deeper cause, such as low voltage or a short-cycling thermostat, we chase that down too.

Power outages and restart failures

Hurricane Ida came ashore on August 29, 2021 and left all of New Orleans without power, while more than 100,000 Cleco customers around Slidell and Covington lost power too. Long outages and repeated restarts are hard on capacitors and contactors, and weak parts often fail the first time power comes back. After any long outage we test both before calling a system healthy, because a unit that hums at restart can overheat its compressor quickly.

How we test and replace them

  1. Power off and dischargeDisconnect off, capacitor safely discharged.
  2. Measure the capacitorEach side checked against its rated microfarads.
  3. Inspect the contactorPoints, coil and any insect debris.
  4. Replace to specNew parts matched for rating, voltage and amps.
  5. Restart and measureAmp draw and start-up checked with the unit running.

What a capacitor or contactor repair costs

  • Which part failed. A capacitor, a contactor or both.
  • Dual or separate capacitors. Some units use two single capacitors instead of one dual.
  • Hard-start kit. An added start capacitor for an older compressor costs extra.
  • Heat-damaged wiring. Burnt terminals or wire add parts and time.
  • Compressor condition. A compressor damaged by long humming needs its own check.

Planning range: about $150 to $400 for a capacitor replacement (source: thisoldhouse.com). It is a market range, not our price; we quote after we see the system.

What you can check before we arrive

Safe to check yourself

  • Set the thermostat to cool, below room temperature
  • Check the breaker and the outdoor disconnect
  • Look, without touching, for a bulged capacitor or ants

Leave to a technician

  • Touching a capacitor; it can hold a dangerous charge with power off
  • Replacing a contactor or any wiring in the unit
  • Testing compressor amp draw after the repair

Common questions

Capacitor and contactor questions

Related ac repair work

Ductless Mini-Split Repair

Dripping heads, error codes and mini-splits that stopped cooling.

Emergency AC Repair

Night, weekend or heat-advisory breakdowns, answered by a person and dispatched.

AC Repair

Warm air, short cycling, odd noises and breakers that will not stay on.

Refrigerant Leak Detection & Repair

Find the leak first, fix it, then charge the system by weight.

Unit humming but not starting? Call now

Switch it off at the thermostat first. Then call and tell us what the outdoor unit is doing.

Answering 24/7(504) 520-4201Tap to call

Call or find us

One number, answered around the clock

Phone
(504) 520-4201
Hours
Open 24 hours, 7 days a week
Service office
3560 Monticello Ave, New Orleans, LA 70118
Head office
12784 Faircrest Dr, Washington, MI 48094
Coverage
New Orleans and the surrounding parishes

Our service office on Monticello Ave, by the Jefferson Parish line.

Call (504) 520-4201