Skip to content
Byron VegasHeating and air, New Orleans Answering 24/7(504) 520-4201

Commercial HVAC

PTAC repair and replacement in New Orleans

Packaged terminal air conditioners, the through-wall units in hotels, apartments and senior housing, fail one room at a time. We troubleshoot and repair them on site, replace units that are past it, and fix the sleeves and drains that cause most leaks.

Answering 24/7 from our Monticello Ave office in New Orleans

  • Answering 24/7
  • Hotels, apartments and senior housing
  • Room-by-room service

Updated October 2026

Short answer

PTAC repair in New Orleans usually means a through-wall unit that is blowing warm, leaking water into the room, tripping its breaker or making noise. Common causes are clogged filters and coils, a blocked drain in the sleeve, a failed fan motor or control board, or low refrigerant. A technician tests the unit in the room, then repairs it or swaps in a match that fits the existing wall sleeve.

Signs a PTAC needs service

Warm airThe unit runs but the room stays warm.
Water on the floorLeaks under or around the sleeve.
Ice on the coilFrost on the indoor coil behind the front panel.
Tripping power cordThe unit trips its breaker or cord protector.
Rattling or buzzingLoose panels, a failing fan or a struggling compressor.

How PTACs fail

Technician removing a PTAC unit from its wall sleeve in a hotel room

PTACs pack a compressor, two coils, fans and controls into one cabinet that slides into a wall sleeve. They run hard in hotel rooms and apartments, filters are often neglected, and the outdoor side faces weather and debris. Dirty coils and filters cause most warm-air and icing complaints.

Many leaks come from the sleeve rather than the unit: a sleeve sloped the wrong way, a blocked drain, or failed caulking around it. We check both before replacing anything, and replacements are matched to the existing sleeve and voltage so the wall does not need opening. We work on Amana, GE Zoneline, Friedrich and other PTAC brands.

PTACs in hotels and apartment buildings

In a building full of PTACs, the job is speed and consistency. We test the failed unit in the room, repair it on the spot when the part is a filter, coil, fan motor or control, and swap in a replacement when the compressor or sealed system has failed. For managers with many units, we can work through a list of rooms on one visit, note the condition of each, and flag units nearing the end so replacements can be budgeted instead of handled one emergency at a time.

PTAC sleeve and drain problems

Water on the floor under a PTAC usually points to the sleeve. The sleeve must slope slightly toward the outside so condensate drains out; if the building settled or the sleeve was set level, water runs back into the room. Drain holes clog with debris, and failed caulking lets rain in around the sleeve. We check the slope, clear the drain, reseal the sleeve to the wall, and confirm the unit sits correctly in it. A leak fixed at the sleeve often saves replacing a unit that was never the problem.

Through-wall units in a long cooling season

Hotels and apartment buildings in New Orleans run their PTACs through a long cooling season, with humidity that keeps coils wet and drains busy, and storm-driven rain that tests every sleeve seal. Units that face the street also collect dust and debris on their outdoor coils. That combination is why filter cleaning, coil cleaning and sleeve checks matter as much as repairs for any building with dozens of through-wall units.

How a PTAC service call runs

  1. Test in the roomRun modes, check airflow, filters and noise.
  2. Check the sleeveSlope, drain holes and the seal to the wall.
  3. Repair or swapFix the part, or fit a matching unit.
  4. ResealSleeve sealed and grille checked outside.
  5. TestCooling, heating and drainage confirmed.

What decides the cost of PTAC work

We have no sourced local range for PTAC work, so here is what moves the price.

  • Repair or replace. Fans and controls cost far less than a new unit.
  • Unit size and voltage. Larger and 265-volt units cost more.
  • Sleeve condition. Reslope, reseal or replace the sleeve as needed.
  • Number of rooms. Working through many rooms on one visit saves trips.
  • Brand match. Some replacements need an exact sleeve and grille match.

What building staff can do

What staff can do

  • Clean or replace the front filter on a schedule
  • Keep curtains and furniture clear of the unit's front
  • Reset a tripped power cord once; if it trips again, take the room out of use

Leave to a technician

  • Opening the cabinet or testing controls
  • Refrigerant and compressor work
  • Pulling units from sleeves or resealing sleeves

PTAC brands we service include Amana, alongside the Carrier, Trane and other systems in the same buildings.

Brands we service and install: Carrier, Trane, Lennox, Rheem, Goodman, American Standard, Daikin, Mitsubishi Electric, Fujitsu, Bryant, Ruud, York, Amana, Honeywell.

Common questions

PTAC questions

Related commercial hvac work

Commercial AC Repair

Rooftop units and split systems for shops, offices and restaurants.

Commercial HVAC Installation

Rooftop unit replacements and new systems for build-outs.

Commercial HVAC Maintenance

Scheduled filters, belts and coil cleaning for business systems.

Commercial Refrigeration Repair

Walk-ins, reach-ins and ice machines for kitchens and bars.

Rooms out of service? Call for room-by-room PTAC repair

Tell us how many rooms are affected and what the units are doing. We will plan the visit to work through them in order.

Answering 24/7(504) 520-4201Tap to call

Call or find us

One number, answered around the clock

Phone
(504) 520-4201
Hours
Open 24 hours, 7 days a week
Service office
3560 Monticello Ave, New Orleans, LA 70118
Head office
12784 Faircrest Dr, Washington, MI 48094
Coverage
New Orleans and the surrounding parishes

Our service office on Monticello Ave, by the Jefferson Parish line.

Call (504) 520-4201